Code Cafe > Height increase Group R occupancy
Check the type of sprinkler system it refers to. Ohio Building Code which is based on IBC states the limit for R use group is for NFPA13R sprinkler system, which is a residential sprinkler system, then you have the 4 story and 60 foot limit.
If you use NFPA13, typical commercial grade sprinklers, then you have the full story and height bonus.
Ran into this on a hotel. Had us running around in circles for weeks thinking we had to go to type IB construction.
Hope this helps.
If you use NFPA13, typical commercial grade sprinklers, then you have the full story and height bonus.
Ran into this on a hotel. Had us running around in circles for weeks thinking we had to go to type IB construction.
Hope this helps.
September 12, 2007 |
Brian McAlexander


FP sprinkler system does not allow increase in number of
stories above 4 in Group R ?